Johnson H05V-R & H07V-R Cable
GENERALLY CONFORMS TO H05V-R & H07V-R, EN 50363-3, EN 50525-2-31, IEC 60227, IEC 60228
Single Core PVC Type TI 1 Insulated Non Sheathed Cable for Internal Wiring
Cable Structure
STRANDED COPPER
PVC TYPE TI-1
Application
H05V-R & H07V-R Cable is used for the installed in a fixed installation mechanically protected, inside a distribution and control device.
Cable Construction
- Conductor: Class 2 Stranded Plain Copper IEC 60228
- Insulation: Special PVC type TI 1 to EN 50363-3
TECHNICAL DATA
Voltage (H05V-R):
300/500 V
Voltage (H07V-R):
450/750 V
Test Voltage (H05V-R):
2000 V
Test Voltage (H07V-R):
2500 V
Short Circuit Temperature:
160°C
Operating Temp Range:
-15°C ❄️ to +70°C 🔥
Flame Propagation:
Flame Retardant test as per IEC 60332-1
Volume Resistivity at 27°C:
Min. 1 x 1010 Ω-cm
Tensile Strength Min.:
12.50 N/mm²
Elongation at Break Min.:
150%
Minimum Bending Radius:
≥ 6 X Cable Dia
CABLE FEATURES
- Design for Harmonized Acc. to European Standards
- Very good Heat Resistance Property for Insulation
- Special Grade Insulation PVC type TI 1 to EN 50363-3
- Very good Insulation Resistance Property
- Excellent Mechanical & Electricals property
- Very good Current carrying capacity
- Very good Thermal property for Insulation
- Flame Retardant
INSULATION COLOR CODE
Black
Red
Blue
Violet
Brown
White
Gray
Green
Orange
Green/Yellow
Pink
Yellow
Or as per customer requirement.
PACKING DETAILS
100 Meter
200 Meter
500 Meter
1000 Meter
2000 Meter
Or as per customer requirement.
Technical Specifications (Single Core H05V-R)
PVC TI 1 Type Insulated & Non Sheathed Round Stranded Bare Copper Cables Specifications
| SIZE (NO. OF CORE X SQ.MM) |
TOTAL NO. OF STRANDS |
MAXIMUM DIA IN MM (NOM.) |
(NOM.) INSULATION THICKNESS mm |
CORE DIA IN mm (APPROX OD) |
MAXIMUM DC RESISTANCE CONDUCTOR AT 20° C Ω/km |
|---|---|---|---|---|---|
| 1 X 0.5 | 7 | 0.300 | 0.60 | 2.10 | 36.00 |
| 1 X 0.75 | 7 | 0.370 | 0.60 | 2.30 | 24.00 |
| 1 X 1.0 | 7 | 0.430 | 0.60 | 2.70 | 18.10 |
Technical Specifications (Single Core H07V-R)
PVC TI 1 Type Insulated & Non Sheathed Round Stranded Bare Copper Cables Specifications
| SIZE (NO. OF CORE X SQ.MM) |
TOTAL NO. OF STRANDS |
MAXIMUM DIA IN MM (NOM.) |
(NOM.) INSULATION THICKNESS mm |
CORE DIA IN mm (APPROX OD) |
MAXIMUM DC RESISTANCE CONDUCTOR AT 20° C Ω/km |
|---|---|---|---|---|---|
| 1 X 1.5 | 7 | 0.52 | 0.70 | 3.00 | 12.10 |
| 1 X 2.5 | 7 | 0.67 | 0.80 | 3.60 | 7.41 |
| 1 X 4 | 7 | 0.85 | 0.80 | 4.10 | 4.61 |
| 1 X 6 | 7 | 1.04 | 0.80 | 5.10 | 3.08 |
| 1 X 10 | 7 | 1.35 | 1.00 | 6.20 | 1.83 |
| 1 X 16 | 7 | 1.71 | 1.00 | 7.40 | 1.15 |
| 1 X 25 | 7 | 2.13 | 1.20 | 9.00 | 0.727 |
| 1 X 35 | 7 | 2.52 | 1.20 | 10.20 | 0.524 |
| 1 X 50 | 19 | 1.83 | 1.40 | 12.20 | 0.387 |
| 1 X 70 | 19 | 2.16 | 1.40 | 14.00 | 0.268 |
| 1 X 95 | 19 | 2.52 | 1.60 | 17.00 | 0.193 |
| 1 X 120 | 37 | 2.03 | 1.60 | 18.00 | 0.153 |
| 1 X 150 | 37 | 2.27 | 1.80 | 20.00 | 0.124 |
| 1 X 185 | 37 | 2.52 | 2.00 | 22.00 | 0.0991 |
| 1 X 240 | 61 | 2.24 | 2.20 | 26.00 | 0.0754 |
| 1 X 300 | 61 | 2.50 | 2.40 | 29.00 | 0.0601 |
| 1 X 400 | 61 | 2.89 | 2.60 | 33.00 | 0.0470 |
IMPORTANT TECHNICAL NOTES