2 Core 1.1 KV Cable

HOME LT POWER CABLES 2 CORE 1.1 KV CABLE
2 Core 1.1 KV Cable
1.1 KV Grade

2 Core 1.1 KV Cable

2 Core Aluminium/Copper Conductor XLPE Insulated Armoured/Un-Armoured Cable (Ref Spec: IS 7098 Part-1)

Cable Structure
Stranded Conductor
Core
XLPE Insulation
Layer 1
PVC Inner Sheath
Layer 2
Armouring
Layer 3

Ref Specification: IS 7098 Part-1 | Cable Code: A2XY-2XY

SIZE
(mm²)
NOMINAL INSULATION THICKNESS (mm) MINIMUM INNER SHEATH THICKNESS (mm) NOMINAL OUTER SHEATH THICKNESS (mm) APPROX OVERALL DIA OF CABLE (±2mm) APPROX WEIGHT OF CABLE (kg/km) MAX CONDUCTOR DC RESISTANCE AT 20°C (Ω/km) NOMINAL CURRENT RATING (AMPS)
A2XY 2XY ALUMINIUM COPPER ALU GROUND ALU AIR COPPER GROUND COPPER AIR
2C x 4 0.70 0.30 1.80 12.00 180 240 7.410 4.610 42 38 54 48
2C x 6 0.70 0.30 1.80 13.00 220 300 4.610 3.080 55 50 67 61
2C x 10 0.70 0.30 1.80 15.00 280 400 3.080 1.830 68 64 89 83
2C x 16 0.70 0.30 1.80 14.00 290 430 1.910 1.150 89 83 115 108
2C x 25 0.90 0.30 2.00 17.00 380 680 1.200 0.727 114 109 147 140
2C x 35 0.90 0.30 2.00 18.50 430 850 0.868 0.524 136 133 176 172
2C x 50 1.00 0.30 2.00 21.00 600 1150 0.641 0.387 161 162 208 208
2C x 70 1.10 0.30 2.00 23.00 750 1520 0.443 0.268 197 204 253 262
2C x 95 1.10 0.40 2.20 26.00 960 2050 0.320 0.193 235 251 302 322
2C x 120 1.20 0.40 2.20 28.00 1160 2450 0.253 0.153 266 287 340 368
2C x 150 1.40 0.40 2.20 31.00 1380 3050 0.206 0.124 296 328 379 419
2C x 185 1.60 0.50 2.40 34.50 1720 3750 0.164 0.0991 335 379 425 482
2C x 240 1.70 0.50 2.60 39.00 2160 4900 0.125 0.0754 385 448 486 566
2C x 300 1.80 0.60 2.80 43.00 2660 6100 0.100 0.0601 432 513 541 644
2C x 400 2.00 0.60 3.00 48.00 3300 7850 0.0778 0.0470 487 593 602 734

Ref Specification: IS 7098 Part-1 | Cable Code: A2XFY/2XFY

SIZE
(mm²)
NOMINAL INSULATION THICKNESS (mm) MINIMUM INNER SHEATH THICKNESS (mm) NOMINAL ARMOUR STRIP (mm) MINIMUM OUTER SHEATH THICKNESS (mm) APPROX OVERALL DIA OF CABLE (±2mm) APPROX WEIGHT OF CABLE (kg/km) MAX CONDUCTOR DC RESISTANCE AT 20°C (Ω/km) NOMINAL CURRENT RATING (AMPS)
A2XFY 2XFY ALUMINIUM COPPER ALU GROUND ALU AIR COPPER GROUND COPPER AIR
2C x 25 0.90 0.30 4 x 0.80 1.40 18.00 610 915 1.200 0.727 114 109 147 140
2C x 35 0.90 0.30 4 x 0.80 1.40 19.50 700 1050 0.868 0.524 136 133 176 172
2C x 50 1.00 0.30 4 x 0.80 1.40 21.50 830 1440 0.641 0.387 161 162 208 208
2C x 70 1.10 0.30 4 x 0.80 1.56 24.50 1060 1910 0.443 0.268 197 204 253 262
2C x 95 1.10 0.40 4 x 0.80 1.56 27.00 1310 2480 0.320 0.193 235 251 302 322
2C x 120 1.20 0.40 4 x 0.80 1.56 29.50 1510 2950 0.253 0.153 266 287 340 368
2C x 150 1.40 0.40 4 x 0.80 1.72 32.00 1760 3610 0.206 0.124 296 328 379 419
2C x 185 1.60 0.50 4 x 0.80 1.72 35.00 2210 4400 0.164 0.0991 335 379 425 482
2C x 240 1.70 0.50 4 x 0.80 1.88 39.50 2610 5500 0.125 0.0754 385 448 486 566
2C x 300 1.80 0.60 4 x 0.80 2.04 43.00 3150 6700 0.100 0.0601 432 513 541 644
2C x 400 2.00 0.60 4 x 0.80 2.36 49.00 4000 8600 0.0778 0.0470 487 593 602 734

Ref Specification: IS 7098 Part-1 | Cable Code: A2XWY/2XWY

SIZE
(mm²)
NOMINAL INSULATION THICKNESS (mm) MINIMUM INNER SHEATH THICKNESS (mm) NOMINAL ARMOUR WIRE (mm) MINIMUM OUTER SHEATH THICKNESS (mm) APPROX OVERALL DIA OF CABLE (±2mm) APPROX WEIGHT OF CABLE (kg/km) MAX CONDUCTOR DC RESISTANCE AT 20°C (Ω/km) NOMINAL CURRENT RATING (AMPS)
A2XWY 2XWY ALUMINIUM COPPER ALU GROUND ALU AIR COPPER GROUND COPPER AIR
2C x 4 0.70 0.30 1.40 1.24 14.00 400 480 7.410 4.610 42 38 54 48
2C x 6 0.70 0.30 1.40 1.24 15.00 470 560 4.610 3.080 55 50 67 61
2C x 10 0.70 0.30 1.40 1.24 16.00 570 710 3.080 1.830 68 64 89 83
2C x 16 0.70 0.30 1.40 1.40 16.00 590 780 1.910 1.150 89 83 115 108
Important Technical Notes
  • Note: 1. The above data is approximate & subject to manufacturing tolerance, 2. Delivery length tolerance +/- 5%.