Johnson H05V-U & H07V-U Cable
GENERALLY CONFORMS TO H05V-U & H07V-U, EN 50363-3, EN 50525-2-31, IEC 60227, IEC 60228
Single Core PVC TI 1 Type Insulated Non Sheathed Cable For Internal Wiring.
Cable Structure
SOLID COPPER
PVC TYPE TI-1
Application
H05V-U & H07V-U Cable is used for the internal wiring in lighting applications. It can also be used in electronic appliances for measuring, regulating and controlling.
Cable Construction
- Conductor: Class 1 Solid bare Copper IEC 60228
- Insulation: PVC type TI 1 to EN 50363-3
TECHNICAL DATA
Voltage (H05V-U):
300/500 V
Voltage (H07V-U):
450/750 V
Test Voltage (H05V-U):
2000 V
Test Voltage (H07V-U):
2500 V
Short Circuit Temperature:
160°C
Operating Temp Range:
-15°C ❄️ to +70°C 🔥
Flame Propagation:
Flame Retardant test as per IEC 60332-1
Volume Resistivity at 27°C Min.:
1 x 1010 Ω-cm
Tensile Strength Min.:
12.50 N/mm²
Elongation at Break Min.:
150%
Minimum Bending Radius:
≥ 8 X Cable Dia
CABLE FEATURES
- Design for Harmonized Acc. to European Standards
- Very good Insulation Resistance Property
- Special Grade Insulation PVC type TI 1 to EN 50363-3
- Excellent Mechanical & Electricals property
- Very good Current carrying capacity
- Very good Thermal property for Insulation
- Flame Retardant
INSULATION COLOR CODE
Black
Red
Blue
Violet
Brown
White
Gray
Green
Orange
Green/Yellow
Pink
Or as per customer requirement.
PACKING DETAILS
100 Meter
200 Meter
500 Meter
1000 Meter
2000 Meter
Or as per customer requirement.
Technical Specifications (Single Core H05V-U)
PVC TI 1 Type Insulated & Non Sheathed Round Solid Bare Copper Cables Specifications
| SIZE (NO. OF CORE X SQ.MM) |
TOTAL NO. OF STRANDS |
MAXIMUM DIA IN MM (NOM.) |
(NOM.) INSULATION THICKNESS mm |
CORE DIA IN mm (APPROX OD) |
MAXIMUM DC RESISTANCE CONDUCTOR AT 20° C Ω/km |
|---|---|---|---|---|---|
| 1 X 0.5 | 1 | 0.80 | 0.60 | 2.10 | 36.00 |
| 1 X 0.75 | 1 | 0.97 | 0.60 | 2.20 | 24.50 |
| 1 X 1.0 | 1 | 1.13 | 0.60 | 2.60 | 18.10 |
Technical Specifications (Single Core H07V-U)
PVC TI 1 Type Insulated & Non Sheathed Round Solid Bare Copper Cables Specifications
| SIZE (NO. OF CORE X SQ.MM) |
TOTAL NO. OF STRANDS |
MAXIMUM DIA IN MM (NOM.) |
(NOM.) INSULATION THICKNESS mm |
CORE DIA IN mm (APPROX OD) |
MAXIMUM DC RESISTANCE CONDUCTOR AT 20° C Ω/km |
|---|---|---|---|---|---|
| 1 X 1.5 | 1 | 1.38 | 0.70 | 3.00 | 12.10 |
| 1 X 2.5 | 1 | 1.78 | 0.80 | 3.60 | 7.41 |
| 1 X 4 | 1 | 2.24 | 0.80 | 4.10 | 4.61 |
| 1 X 6 | 1 | 2.77 | 0.80 | 4.80 | 3.08 |
| 1 X 10 | 1 | 3.57 | 1.00 | 5.80 | 1.83 |
IMPORTANT TECHNICAL NOTES
NOTE: The Above Data is Approximate & Subject to Manufacturing Tolerance. The number of wire is approximate and wire diameter is nominal, They shall be such as to satisfy the requirements of conductor resistance of IEC 60228/DIN VDE 0295/IS 8130/BS 6360.