H05V2-U & H07V2-U Cable

HOME EXPORT CABLES H05V2-U & H07V2-U CABLE
Johnson H05V2-U & H07V2-U Cable

Johnson H05V2-U & H07V2-U Cable

GENERALLY CONFORMS TO H05V2-U & H07V2-U, EN 50363-3, EN 50525-2-31, IEC 60227, IEC 60228

Single Core Heat Resistance HR PVC TI 3 Type Insulated Non Sheathed Cable For Internal Wiring.

Cable Structure
SOLID COPPER
Conductor
HR PVC TYPE TI-3
Insulation
Application

H05V2-U & H07V2-U Cable is used for the internal wiring in lighting applications. It can also be used in electronic appliances for measuring, regulating and controlling.

Cable Construction
  • Conductor: Class 1 Solid bare Copper IEC 60228
  • Insulation: HR PVC type TI 3 to EN 50363-3

TECHNICAL DATA

Voltage (H05V2-U): 300/500 V
Voltage (H07V2-U): 450/750 V
Test Voltage (H05V2-U): 2000 V
Test Voltage (H07V2-U): 2500 V
Short Circuit Temperature: 160°C
Operating Temp Range: -15°C ❄️ to +90°C 🔥
Flame Propagation: Flame Retardant test as per IEC 60332-1
Volume Resistivity at 27°C Min.: 1 x 1010 Ω-cm
Tensile Strength Min.: 12.50 N/mm²
Elongation at Break Min.: 150%
Minimum Bending Radius: ≥ 8 X Cable Dia

CABLE FEATURES

  • Design for Harmonized Acc. to European Standards
  • Very good Heat Resistance Property for Insulation
  • Very good Insulation Resistance Property
  • Special Grade Insulation HR PVC type TI 3 to EN 50363-3
  • Excellent Mechanical & Electricals property
  • Very good Current carrying capacity
  • Very good Thermal property for Insulation
  • Flame Retardant
INSULATION COLOR CODE
Black Red Blue Violet Brown White Gray Green Orange Green/Yellow Pink

Or as per customer requirement.

PACKING DETAILS
Standard & Custom
100 Meter
200 Meter
500 Meter
1000 Meter
2000 Meter

Or as per customer requirement.


Technical Specifications (Single Core H05V2-U)

HR PVC TI 3 Type Insulated & Non Sheathed Round Solid Bare Copper Cables Specifications

SIZE
(NO. OF CORE X SQ.MM)
TOTAL
NO. OF STRANDS
MAXIMUM
DIA IN MM (NOM.)
(NOM.) INSULATION
THICKNESS mm
CORE DIA IN mm
(APPROX OD)
MAXIMUM DC RESISTANCE CONDUCTOR AT 20° C
Ω/km
1 X 0.510.800.602.1036.00
1 X 0.7510.970.602.2024.50
1 X 1.011.130.602.6018.10

Technical Specifications (Single Core H07V2-U)

HR PVC TI 3 Type Insulated & Non Sheathed Round Solid Bare Copper Cables Specifications

SIZE
(NO. OF CORE X SQ.MM)
TOTAL
NO. OF STRANDS
MAXIMUM
DIA IN MM (NOM.)
(NOM.) INSULATION
THICKNESS mm
CORE DIA IN mm
(APPROX OD)
MAXIMUM DC RESISTANCE CONDUCTOR AT 20° C
Ω/km
1 X 1.511.380.703.0012.10
1 X 2.511.780.803.607.41
1 X 412.240.804.104.61
1 X 612.770.804.803.08
1 X 1013.571.005.801.83
IMPORTANT TECHNICAL NOTES
NOTE: The Above Data is Approximate & Subject to Manufacturing Tolerance. The number of wire is approximate and wire diameter is nominal, They shall be such as to satisfy the requirements of conductor resistance of IEC 60228/DIN VDE 0295/IS 8130/BS 6360.